Water and corrosion-resistant, this sample draw sensor is the answer to your system maintenance needs. Featuring a built-in pump powered from 24 V DC, this sensor performs single-person calibrations and remote sampling at up to 5000' from a controller, and interfaces to any RKI or third-party control systems.
Water and corrosion-resistant, this sample draw sensor is the answer to your system maintenance needs. Featuring a built-in pump powered from 24 V DC, this sensor performs single-person calibrations and remote sampling at up to 5000' from a controller, and interfaces to any RKI or third-party control systems.
Features
Applications
Target Gas and Detection Range | Methane (CH4): 0 to 100% LEL |
Input Power | 24 V DC nominal (18.5 V DC to 30 V DC) |
Sampling Method | Sample-draw |
Sample Flow | 3.0 SCFH typical, with no inlet or exhaust line |
Flow to Sensor | 1.0 SCFH (nominal) |
Low Flow Setpoint | 0.6 ±0.1 SCFH |
Response Time | 90% in 30 seconds |
Accuracy | ±5% of reading or ±2% LEL (whichever is greater) |
Construction (Housing) | Fibreglass/polyester (NEMA 4X) |
Dimensions | 8.5 x 6.5 x 4.25" (215.9 x 165.1 x 107.9 mm) |
Target Gas and Detection Range | Methane (CH4): 0 to 100% LEL |
Input Power | 24 V DC nominal (18.5 V DC to 30 V DC) |
Sampling Method | Sample-draw |
Sample Flow | 3.0 SCFH typical, with no inlet or exhaust line |
Flow to Sensor | 1.0 SCFH (nominal) |
Low Flow Setpoint | 0.6 ±0.1 SCFH |
Response Time | 90% in 30 seconds |
Accuracy | ±5% of reading or ±2% LEL (whichever is greater) |
Construction (Housing) | Fibreglass/polyester (NEMA 4X) |
Dimensions | 8.5 x 6.5 x 4.25" (215.9 x 165.1 x 107.9 mm) |